Tigo EI Inverter Manual

Installation manual for the Tigo EI Inverter, including instructions for the EI Battery, ATS, and Energy Meter

Wiring the Meter

Thank you! Your submission has been received!
Oops! Something went wrong while submitting the form.

Tools required: 1/8” flathead screwdriver, cable ties

Supplies required: conduit and associated water-tight fittings, two 18-22AWG conductors, 10-20A over current protection device

The energy meter includes 2CTs which monitor the current and direction of energy flow from the grid. Three conductors terminated at an over current protection device in the main service panel monitor the grid voltage. This data is sent to the inverter via a 3-wire CAT5/6cable.

Table 8 Energy meter cable/conductor schedule

Figure 51 Energy Meter wiring diagram

This meter is considered “permanently connected equipment ”and requires a disconnect means. The meter draws 10-30mA therefore the rating of the overcurrent protection is based on the size of the conductors used. Use a circuit breaker or fuse rated for 20A or less.

1)   Verify the power is OFF before making connections.

2)   Connect the AC conductors to the 4-pin connector.

      a.   Loosen the appropriate screws on the 4-pin connector.

      b.   Connect each AC conductor to the appropriate screw terminal of the connector:

L1 – red, L2 – black, neutral – white, ground - green

      c.   Tighten the screws 0.4Nm, making sure the conductors are fully inserted and cannot be easily pulled out.

      d.   Insert the 5-pin connector into the terminal on the meter making sure it is fully seated.

      e.   Complete the installation of the AC conductors by terminating the opposite end of the conductors at an overcurrent protection device (20A or less) in the load center.

3)   Connect the CT conductors to the 4-pin connector of Block 1:

      a.   Loosen the pins of the 4-pin connector of Block1.

      b.   Connect the blue and brown conductors to the connector as shown in the diagram:

CT1 blue – 1, CT1 brown – 2, CT2 blue – 3, CT2 brown – 4

      c.   Tighten the screws making sure the conductors are fully inserted and cannot be easily pulled out.

      d.   Insert the 4-pin connector into the Block 1terminal on the meter making sure it is fully seated.

      e.   Clamp the CTs around the Grid conductors feeding the main service panel:

CT1 – L1, CT2 – L2

      f.    Secure the clamping CTs with a cable tie to ensure it does not become loose or open.

4)   Connect the RS485 twisted pair cable to the 4-pin connector of Block 2:

      a.   Loosen the pins of the 4-pin connector of Block 2.

      b.   Connect conductors to the A+, B-, and GND positions on the connector

A+ red - 2, B- black - 3, shield green – 4 (position 1 is open).

      c.   Tighten the screws making sure the conductors are fully inserted and cannot be easily pulled out.

      d.   Insert the 4-pin connector into the Block 2 terminal on the meter making sure it is fully seated.

Figure 52 Energy meter communications connection

1)   Connect the RS485 twisted pair cable to the3-pin connector in the inverter:

     a.   Run conduit from the load center to the inverter. Use appropriate conduit fittings to ensure a water-tight seal.

      b.   Loosen the pins of the 3-pin connector included with the inverter accessories (J).

      c.   Connect conductors to the A+, B-, and GND positions on the connector

A+ red - 1, shield green – 2, B- black - 3

      d.   Tighten the screws making sure the conductors are fully inserted and cannot be easily pulled out.

      e.   Insert the 3-pin connector into the inverter’s 3-pinterminal on the communication board making sure it is fully seated.